| IAQ Logger | Specifications |
|---|---|
![]() |
The IAQ Logger, when combined with the Telaire 7001 Handheld CO2 Monitor, records the three leading indicators of indoor air quality: (1) temperature, (2) relative humidity, and (3) carbon dioxide. |
| Size | 107 mm x 74 mm x 22mm (4.2กจ x 2.9กจ x 0.9กจ) |
| Weight | 110 g (3.75 oz) |
| Case Material | NorylR plastic |
| Operating Limits | -40 to 70oC (-40 to 158oF) and 0 to 95% RH (non-condensing) |
| Battery | 3.6 volt Lithium |
| Battery Life | 10 years under normal use (factory replaceable) |
| Memory Size | 32 KB (32,767 readings) |
| Sampling Methods | 1. Continuous (First-in, First out) 2. Stop when full (Fill-then-stop) |
| Sampling Rates | From 8 seconds to once every 5 days |
| Resolution | 8-bit (1 part in 256) |
| PC Requirements | IBM PC or 100% compatible with at least 2 MB RAM, 2 MB of hard drive disk space and one free serial port |
| Software Requirements | TrendReaderR Standard 2 - compatible with Windows 2000, XP and Vista (Home Premium and above) |