PowerWatch120V |
PowerWatch220-240V |
PowerWatch120V | Specifications | |
---|---|---|
![]() |
PowerWatch 120V is the easiest way to monitor and record essential voltage disturbance information from any North American power receptacle. Just set up your pre-determined disturbance threshold values or use the industry standard default values and plug it in. No wiring or dangerous connections required. | |
Hot to Neutral | Neutral to Ground | |
Surge, Sag & Outage | ||
Range | 0 to 200 V rms | 3 to 200 V rms |
Accuracy | +/- 1 V rms + resolution | +/- 1 V rms + resolution |
Resolution | 1 V rms | 1 V rms |
Impulse | ||
Range | 100 to 2500 V peak | 50 to 2500 V peak |
Accuracy | +/- 10% of reading + resolution | +/- 10% of reading + resolution |
Resolution | 10 V | 10 V |
Width Detection | 1 £gsec minimum | 1 £gsec minimum |
Phase Angle Accuracy | +/- 1¢X (20 to 180¢X, 200 to 360¢X) | +/- 1¢X (20 to 180¢X, 200 to 360¢X) |
Phase Angle Resolution | 1¢X | 1¢X |
Frequency | ||
Range | 45 to 65 Hz | |
Accuracy | +/- 0.1 Hz (3 cycles minimum) | |
Resolution | 0.1 Hz | |
Time Events (< 1 sec) | ||
Accuracy | +/- 0.5 cycle | +/- 1 cycle |
Resolution | 0.5 cycle | 1 cycle |
Time Stamp (> 1 sec) | ||
Accuracy | +/- 2 seconds/day + resolution | |
Resolution | 8 seconds |